{"product_id":"ls-electric-susol-ts-mtu-motor-protection-mccb","title":"LS Electric Susol TS MTU Motor Protection MCCB (1.6-630 A, 3P)","description":"\u003cp class=\"ps-intro\"\u003eLS Electric Susol TS100 to TS800 motor-protection molded case circuit breakers with MTU magnetic-only trip unit, 1.6-630 A, 3 poles, for short-circuit protection of motor feeders combined with a contactor and overload relay.\u003c\/p\u003e\u003ch4 class=\"ps-h\"\u003eKey features\u003c\/h4\u003e\u003cul class=\"ps-feat\"\u003e\n\u003cli\u003eMTU magnetic-only trip unit: instantaneous Ii adjustable 6...12 x In in 6 steps, no thermal (overload) element\u003c\/li\u003e\n\u003cli\u003eDesigned for motor starters together with a magnetic contactor and thermal overload relay\u003c\/li\u003e\n\u003cli\u003eBreaking capacity at 380\/415 V: N 50\/65 kA, H 85\/100 kA, L 150 kA depending on frame (Ics = 100% Icu)\u003c\/li\u003e\n\u003cli\u003eFrames TS100, TS160, TS250 (105 x 160 x 86 mm), TS400\/TS630 (140 x 260 x 110 mm), TS800 (210 x 320 x 135 mm)\u003c\/li\u003e\n\u003cli\u003eAccepts the common Susol internal and external accessories (AX, AL, SHT, UVT, handles, motor operator)\u003c\/li\u003e\n\u003cli\u003eOrdering format: frame + type + MTU + In + poles (e.g. TS250N-MTU-220A-3P)\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch4 class=\"ps-h\"\u003eSpecifications\u003c\/h4\u003e\u003ctable class=\"ps-kv\"\u003e\u003ctbody\u003e\n\u003ctr\u003e\n\u003cth\u003eFrame size\u003c\/th\u003e\n\u003ctd\u003e100 \/ 160 \/ 250 \/ 400 \/ 630 \/ 800 AF\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003ePoles\u003c\/th\u003e\n\u003ctd\u003e3P\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eRated operational voltage (Ue)\u003c\/th\u003e\n\u003ctd\u003eAC 690 V, 50\/60 Hz; DC 500 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eRated insulation voltage (Ui)\u003c\/th\u003e\n\u003ctd\u003eAC 1000 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eRated impulse voltage (Uimp)\u003c\/th\u003e\n\u003ctd\u003e8 kV\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eIcu at 220\/240 V\u003c\/th\u003e\n\u003ctd\u003eN 100 kA, H 120 kA, L 200 kA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eTrip unit\u003c\/th\u003e\n\u003ctd\u003eMTU, magnetic only (instantaneous adjustable)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eUtilization category\u003c\/th\u003e\n\u003ctd\u003eA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eMounting\u003c\/th\u003e\n\u003ctd\u003eFixed, front connection (plug-in available)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eStandards\u003c\/th\u003e\n\u003ctd\u003eIEC 60947-2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eSource\u003c\/th\u003e\n\u003ctd\u003eLS Electric Susol MCCB catalog C01091-24 (2025-09), p. 33 (A-1-10), 78-81 (A-2-43 to A-2-46)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\u003c\/table\u003e\u003ctable class=\"ps-src\"\u003e\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100N-MTU-1.6A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: N (Normal), 50 kA at 415 V | Rated current In: 1.6 A | Instantaneous Ii: 10-20 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100N-MTU-3.2A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: N (Normal), 50 kA at 415 V | Rated current In: 3.2 A | Instantaneous Ii: 20-40 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100N-MTU-6.3A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: N (Normal), 50 kA at 415 V | Rated current In: 6.3 A | Instantaneous Ii: 40-80 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100N-MTU-12A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: N (Normal), 50 kA at 415 V | Rated current In: 12 A | Instantaneous Ii: 70-140 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100N-MTU-20A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: N (Normal), 50 kA at 415 V | Rated current In: 20 A | Instantaneous Ii: 120-240 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100N-MTU-32A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: N (Normal), 50 kA at 415 V | Rated current In: 32 A | Instantaneous Ii: 190-380 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100N-MTU-50A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: N (Normal), 50 kA at 415 V | Rated current In: 50 A | Instantaneous Ii: 300-600 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100N-MTU-63A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: N (Normal), 50 kA at 415 V | Rated current In: 63 A | Instantaneous Ii: 400-800 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100N-MTU-100A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: N (Normal), 50 kA at 415 V | Rated current In: 100 A | Instantaneous Ii: 600-1200 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100H-MTU-1.6A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 1.6 A | Instantaneous Ii: 10-20 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100H-MTU-3.2A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 3.2 A | Instantaneous Ii: 20-40 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100H-MTU-6.3A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 6.3 A | Instantaneous Ii: 40-80 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100H-MTU-12A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 12 A | Instantaneous Ii: 70-140 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100H-MTU-20A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 20 A | Instantaneous Ii: 120-240 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100H-MTU-32A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 32 A | Instantaneous Ii: 190-380 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100H-MTU-50A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 50 A | Instantaneous Ii: 300-600 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100H-MTU-63A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 63 A | Instantaneous Ii: 400-800 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100H-MTU-100A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 100 A | Instantaneous Ii: 600-1200 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100L-MTU-1.6A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 1.6 A | Instantaneous Ii: 10-20 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100L-MTU-3.2A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 3.2 A | Instantaneous Ii: 20-40 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100L-MTU-6.3A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 6.3 A | Instantaneous Ii: 40-80 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100L-MTU-12A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 12 A | Instantaneous Ii: 70-140 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100L-MTU-20A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 20 A | Instantaneous Ii: 120-240 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100L-MTU-32A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 32 A | Instantaneous Ii: 190-380 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100L-MTU-50A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 50 A | Instantaneous Ii: 300-600 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100L-MTU-63A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 63 A | Instantaneous Ii: 400-800 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS100L-MTU-100A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS100 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 100 A | Instantaneous Ii: 600-1200 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS160N-MTU-32A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS160 | Breaking capacity: N (Normal), 50 kA at 415 V | Rated current In: 32 A | Instantaneous Ii: 190-380 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS160N-MTU-50A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS160 | Breaking capacity: N (Normal), 50 kA at 415 V | Rated current In: 50 A | Instantaneous Ii: 300-600 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS160N-MTU-63A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS160 | Breaking capacity: N (Normal), 50 kA at 415 V | Rated current In: 63 A | Instantaneous Ii: 400-800 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS160N-MTU-100A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS160 | Breaking capacity: N (Normal), 50 kA at 415 V | Rated current In: 100 A | Instantaneous Ii: 600-1200 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS160N-MTU-160A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS160 | Breaking capacity: N (Normal), 50 kA at 415 V | Rated current In: 160 A | Instantaneous Ii: 960-1920 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS160H-MTU-32A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS160 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 32 A | Instantaneous Ii: 190-380 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS160H-MTU-50A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS160 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 50 A | Instantaneous Ii: 300-600 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS160H-MTU-63A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS160 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 63 A | Instantaneous Ii: 400-800 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS160H-MTU-100A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS160 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 100 A | Instantaneous Ii: 600-1200 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS160H-MTU-160A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS160 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 160 A | Instantaneous Ii: 960-1920 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS160L-MTU-32A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS160 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 32 A | Instantaneous Ii: 190-380 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS160L-MTU-50A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS160 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 50 A | Instantaneous Ii: 300-600 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS160L-MTU-63A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS160 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 63 A | Instantaneous Ii: 400-800 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS160L-MTU-100A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS160 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 100 A | Instantaneous Ii: 600-1200 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS160L-MTU-160A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS160 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 160 A | Instantaneous Ii: 960-1920 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS250N-MTU-100A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS250 | Breaking capacity: N (Normal), 50 kA at 415 V | Rated current In: 100 A | Instantaneous Ii: 600-1200 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS250N-MTU-160A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS250 | Breaking capacity: N (Normal), 50 kA at 415 V | Rated current In: 160 A | Instantaneous Ii: 960-1920 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS250N-MTU-220A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS250 | Breaking capacity: N (Normal), 50 kA at 415 V | Rated current In: 220 A | Instantaneous Ii: 1320-2640 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS250H-MTU-100A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS250 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 100 A | Instantaneous Ii: 600-1200 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS250H-MTU-160A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS250 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 160 A | Instantaneous Ii: 960-1920 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS250H-MTU-220A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS250 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 220 A | Instantaneous Ii: 1320-2640 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS250L-MTU-100A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS250 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 100 A | Instantaneous Ii: 600-1200 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS250L-MTU-160A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS250 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 160 A | Instantaneous Ii: 960-1920 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS250L-MTU-220A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS250 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 220 A | Instantaneous Ii: 1320-2640 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS400N-MTU-320A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS400 | Breaking capacity: N (Normal), 65 kA at 415 V | Rated current In: 320 A | Instantaneous Ii: 1920-3840 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS400H-MTU-320A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS400 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 320 A | Instantaneous Ii: 1920-3840 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS400L-MTU-320A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS400 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 320 A | Instantaneous Ii: 1920-3840 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS630N-MTU-500A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS630 | Breaking capacity: N (Normal), 65 kA at 415 V | Rated current In: 500 A | Instantaneous Ii: 3000-6000 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS630H-MTU-500A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS630 | Breaking capacity: H (High), 85 kA at 415 V | Rated current In: 500 A | Instantaneous Ii: 3000-6000 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS630L-MTU-500A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS630 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 500 A | Instantaneous Ii: 3000-6000 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS800N-MTU-630A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS800 | Breaking capacity: N (Normal), 65 kA at 415 V | Rated current In: 630 A | Instantaneous Ii: 3780-7560 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS800H-MTU-630A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS800 | Breaking capacity: H (High), 100 kA at 415 V | Rated current In: 630 A | Instantaneous Ii: 3780-7560 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTS800L-MTU-630A-3P\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eFrame: TS800 | Breaking capacity: L (Current limiting), 150 kA at 415 V | Rated current In: 630 A | Instantaneous Ii: 3780-7560 A (6 steps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\u003c\/table\u003e","brand":"LS Electric","offers":[{"title":"Default Title","offer_id":67521960182050,"sku":"TS100N-MTU-1.6A-3P","price":0.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/1021\/0744\/7586\/files\/ls-electric-susol-ts-mtu-motor-protection-mccb.jpg?v=1791954616","url":"https:\/\/prosourcemro.com\/products\/ls-electric-susol-ts-mtu-motor-protection-mccb","provider":"ProSource MRO","version":"1.0","type":"link"}