{"product_id":"mitsubishi-electric-ms-t-n-series-mso-n400dl-delay-open-magnetic-starter","title":"Mitsubishi Electric MSO-N400DL Delay-Open Magnetic Starter (105-330A)","description":"\u003cp class=\"ps-intro\"\u003eThe Mitsubishi Electric MSO-N400DL is an MS-T\/N series delay-open magnetic starter that keeps the motor circuit closed through momentary power failures.\u003c\/p\u003e\u003ch4 class=\"ps-h\"\u003eKey features\u003c\/h4\u003e\u003cul class=\"ps-feat\"\u003e\n\u003cli\u003eHolds the contactor closed for 2 (+2\/-1) s during momentary power failures or voltage dips\u003c\/li\u003e\n\u003cli\u003eCapacitor-backed coil circuit - no re-closing operation needed after the dip, load keeps running\u003c\/li\u003e\n\u003cli\u003eFor lighting, building automation and other circuits that must ride through brief outages\u003c\/li\u003e\n\u003cli\u003eRated AC-3 capacity 110 \/ 200 \/ 200 kW at 220\/440\/550V; heaters 105A-330A\u003c\/li\u003e\n\u003cli\u003eOperation coil AC100V (100-110V) or AC200V (200-220V); main-circuit rated voltage must be specified at order\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch4 class=\"ps-h\"\u003eSpecifications\u003c\/h4\u003e\u003ctable class=\"ps-kv\"\u003e\u003ctbody\u003e\n\u003ctr\u003e\n\u003cth\u003eSeries\u003c\/th\u003e\n\u003ctd\u003eMS-T\/N\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eFrame\u003c\/th\u003e\n\u003ctd\u003eN400\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eConstruction\u003c\/th\u003e\n\u003ctd\u003eOpen type\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eRated capacity AC-3 (200\/400\/500V)\u003c\/th\u003e\n\u003ctd\u003e110\/200\/200 kW\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eRated current AC-3 (220\/440\/550V)\u003c\/th\u003e\n\u003ctd\u003e400\/400\/350 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eDelay time\u003c\/th\u003e\n\u003ctd\u003e2 (+2\/-1) s fixed\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eAuxiliary contacts\u003c\/th\u003e\n\u003ctd\u003e1a1b\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eThermal relay\u003c\/th\u003e\n\u003ctd\u003eTH-N400RH\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eModel\u003c\/th\u003e\n\u003ctd\u003eMSO-N400DL\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eSource\u003c\/th\u003e\n\u003ctd\u003eMitsubishi Electric MS-T\/N Series catalogue (Korea ed.), p. 110-111, 124, 127\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\u003c\/table\u003e\u003ctable class=\"ps-src\"\u003e\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eMSO-N400DL 105A AC100V\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eHeater: 105A | Setting range: 85-125A | Coil: AC100V | Coil rating: 100-110V 50\/60Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMSO-N400DL 105A AC200V\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eHeater: 105A | Setting range: 85-125A | Coil: AC200V | Coil rating: 200-220V 50\/60Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMSO-N400DL 125A AC100V\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eHeater: 125A | Setting range: 100-150A | Coil: AC100V | Coil rating: 100-110V 50\/60Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMSO-N400DL 125A AC200V\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eHeater: 125A | Setting range: 100-150A | Coil: AC200V | Coil rating: 200-220V 50\/60Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMSO-N400DL 150A AC100V\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eHeater: 150A | Setting range: 120-180A | Coil: AC100V | Coil rating: 100-110V 50\/60Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMSO-N400DL 150A AC200V\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eHeater: 150A | Setting range: 120-180A | Coil: AC200V | Coil rating: 200-220V 50\/60Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMSO-N400DL 180A AC100V\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eHeater: 180A | Setting range: 140-220A | Coil: AC100V | Coil rating: 100-110V 50\/60Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMSO-N400DL 180A AC200V\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eHeater: 180A | Setting range: 140-220A | Coil: AC200V | Coil rating: 200-220V 50\/60Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMSO-N400DL 250A AC100V\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eHeater: 250A | Setting range: 200-300A | Coil: AC100V | Coil rating: 100-110V 50\/60Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMSO-N400DL 250A AC200V\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eHeater: 250A | Setting range: 200-300A | Coil: AC200V | Coil rating: 200-220V 50\/60Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMSO-N400DL 330A AC100V\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eHeater: 330A | Setting range: 260-400A | Coil: AC100V | Coil rating: 100-110V 50\/60Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMSO-N400DL 330A AC200V\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eHeater: 330A | Setting range: 260-400A | Coil: AC200V | Coil rating: 200-220V 50\/60Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\u003c\/table\u003e","brand":"Mitsubishi Electric","offers":[{"title":"Default Title","offer_id":67534140899618,"sku":"MSO-N400DL 105A AC100V","price":0.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/1021\/0744\/7586\/files\/Mstn-starter-n150-1_b2ebb156-446f-4f69-a78c-23a1373170a7.png?v=1790662672","url":"https:\/\/prosourcemro.com\/products\/mitsubishi-electric-ms-t-n-series-mso-n400dl-delay-open-magnetic-starter","provider":"ProSource MRO","version":"1.0","type":"link"}