{"product_id":"siemens-sentron-5sd74-lightning-arresters-type-1","title":"Siemens SENTRON 5SD74 lightning arresters, type 1","description":"\u003cp class=\"ps-intro\"\u003eSENTRON 5SD74 type 1 lightning current arresters with remote signaling for TN-C, TN-S, TT and IT systems at the building service entrance.\u003c\/p\u003e\u003ch4 class=\"ps-h\"\u003eKey features\u003c\/h4\u003e\u003cul class=\"ps-feat\"\u003e\n\u003cli\u003eType 1 lightning current arresters per IEC\/EN 61643-11\u003c\/li\u003e\n\u003cli\u003eVersions for TN-C, TN-S\/TT systems and IT networks up to 690 V AC\u003c\/li\u003e\n\u003cli\u003eCircuits 1+0, 1+1, 3+0 and 3+1\u003c\/li\u003e\n\u003cli\u003eRemote signaling contact for status monitoring\u003c\/li\u003e\n\u003cli\u003eReplaceable spare part plugs\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch4 class=\"ps-h\"\u003eSpecifications\u003c\/h4\u003e\u003ctable class=\"ps-kv\"\u003e\u003ctbody\u003e\n\u003ctr\u003e\n\u003cth\u003eBrand\u003c\/th\u003e\n\u003ctd\u003eSiemens SENTRON\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eSeries\u003c\/th\u003e\n\u003ctd\u003e5SD74\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eSPD type\u003c\/th\u003e\n\u003ctd\u003eType 1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eStandards\u003c\/th\u003e\n\u003ctd\u003eIEC\/EN 61643-11\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eMounting\u003c\/th\u003e\n\u003ctd\u003eDIN rail\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eSource\u003c\/th\u003e\n\u003ctd\u003eSiemens Catalog LV 10 · 2026, p. 508-509\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\u003c\/table\u003e\u003ctable class=\"ps-src\"\u003e\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e5SD7411-2\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSystem: TN-C and IT | Protection paths: L-PE | Un \/ Uc: 690 V AC \/ 800 V AC | Circuit: 1 + 0 | Remote signaling: Yes | Mounting width: No modular device\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e5SD7412-1\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSystem: TN-S and TT | Protection paths: L-N, L-PE and N-PE | Un \/ Uc: 240 V AC \/ 350 V AC | Circuit: 1 + 1 | Remote signaling: Yes | Mounting width: 4 MW\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e5SD7413-1\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSystem: TN-C | Protection paths: L-PEN | Un \/ Uc: 240\/415 V AC \/ 350 V AC | Circuit: 3 + 0 | Remote signaling: Yes | Mounting width: 6 MW\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e5SD7414-1\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSystem: TN-S and TT | Protection paths: L-N, L-PE and N-PE | Un \/ Uc: 240\/415 V AC \/ 350 V AC | Circuit: 3 + 1 | Remote signaling: Yes | Mounting width: 8 MW\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e5SD7418-0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSystem: Spare part plug | Protection paths: N-PE | Un \/ Uc: - | Circuit: For 5SD7412-1\/14-1, 5SD7442-1\/44-1 | Remote signaling: - | Mounting width: -\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e5SD7418-1\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSystem: Spare part plug | Protection paths: L-N and L-PEN | Un \/ Uc: - | Circuit: For 5SD7412-1, 5SD7413-1, 5SD7414-1 | Remote signaling: - | Mounting width: -\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\u003c\/table\u003e","brand":"Siemens","offers":[{"title":"Default Title","offer_id":67535326970146,"sku":"5SD7411-2","price":0.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/1021\/0744\/7586\/files\/siemens-sentron-5sd74-lightning-arresters-type-1.jpg?v=1792150079","url":"https:\/\/prosourcemro.com\/products\/siemens-sentron-5sd74-lightning-arresters-type-1","provider":"ProSource MRO","version":"1.0","type":"link"}