{"product_id":"siemens-sirius-3rv24-circuit-breakers-transformer-protection","title":"Siemens SIRIUS 3RV24 Circuit Breakers for Transformer Protection","description":"\u003cp class=\"ps-intro\"\u003eSIRIUS 3RV24 circuit breakers protect transformers with high inrush currents, with raised instantaneous release settings in sizes S00 to S2.\u003c\/p\u003e\u003ch4 class=\"ps-h\"\u003eKey features\u003c\/h4\u003e\u003cul class=\"ps-feat\"\u003e\n\u003cli\u003eInstantaneous release set approx. 20x In to ride through transformer inrush\u003c\/li\u003e\n\u003cli\u003eClass 10 adjustable thermal overload release, 0.11 A to 65 A\u003c\/li\u003e\n\u003cli\u003eShort-circuit breaking capacity up to 100 kA at 400 V AC\u003c\/li\u003e\n\u003cli\u003eVersions without phase-failure detection for 1-, 2- and 3-phase loads (-0DA0)\u003c\/li\u003e\n\u003cli\u003eScrew or spring-loaded terminals; versions with transverse auxiliary switch 1 NO + 1 NC\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch4 class=\"ps-h\"\u003eSpecifications\u003c\/h4\u003e\u003ctable class=\"ps-kv\"\u003e\u003ctbody\u003e\n\u003ctr\u003e\n\u003cth\u003eProduct line\u003c\/th\u003e\n\u003ctd\u003eSIRIUS 3RV2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eClass\u003c\/th\u003e\n\u003ctd\u003e10\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eApplication\u003c\/th\u003e\n\u003ctd\u003eTransformers with high inrush current\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eBrand\u003c\/th\u003e\n\u003ctd\u003eSiemens\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eCatalog section\u003c\/th\u003e\n\u003ctd\u003eIC 10 ch. 7 Protection equipment\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eCategory\u003c\/th\u003e\n\u003ctd\u003eMotor Starter Protectors\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003ePoles\u003c\/th\u003e\n\u003ctd\u003e3\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eRated frequency\u003c\/th\u003e\n\u003ctd\u003e50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eMounting\u003c\/th\u003e\n\u003ctd\u003eDIN rail or screw fixing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eSource\u003c\/th\u003e\n\u003ctd\u003eSiemens Catalog IC 10 · 2026, p. 7\/38-7\/41\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\u003c\/table\u003e\u003ctable class=\"ps-src\"\u003e\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0AA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.11–0.16 A | Inst. release: 3.3 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0AA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.11–0.16 A | Inst. release: 3.3 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0BA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.14–0.2 A | Inst. release: 4.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0BA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.14–0.2 A | Inst. release: 4.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0CA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.18–0.25 A | Inst. release: 5.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0CA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.18–0.25 A | Inst. release: 5.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0DA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.22–0.32 A | Inst. release: 6.5 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0DA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.22–0.32 A | Inst. release: 6.5 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0EA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.28–0.4 A | Inst. release: 8.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0EA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.28–0.4 A | Inst. release: 8.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0FA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.35–0.5 A | Inst. release: 10 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0FA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.35–0.5 A | Inst. release: 10 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0GA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.45–0.63 A | Inst. release: 13 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0GA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.45–0.63 A | Inst. release: 13 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0HA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.55–0.8 A | Inst. release: 16 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0HA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.55–0.8 A | Inst. release: 16 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0JA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.7–1 A | Inst. release: 21 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0JA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.7–1 A | Inst. release: 21 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0KA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.9–1.25 A | Inst. release: 26 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0KA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.9–1.25 A | Inst. release: 26 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1AA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 1.1–1.6 A | Inst. release: 33 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1AA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 1.1–1.6 A | Inst. release: 33 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1BA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 1.4–2 A | Inst. release: 42 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1BA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 1.4–2 A | Inst. release: 42 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1CA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1CA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1DA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 2.2–3.2 A | Inst. release: 65 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1DA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 2.2–3.2 A | Inst. release: 65 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1EA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 2.8–4 A | Inst. release: 82 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1EA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 2.8–4 A | Inst. release: 82 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1FA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 3.5–5 A | Inst. release: 104 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1FA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 3.5–5 A | Inst. release: 104 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1GA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1GA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1HA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1HA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1JA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1JA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1KA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 9–12.5 A | Inst. release: 260 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1KA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 9–12.5 A | Inst. release: 260 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-4AA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-4AA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0EA20-0DA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.28–0.4 A | Inst. release: 8.2 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1AA20-0DA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 1.1–1.6 A | Inst. release: 33 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1BA20-0DA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 1.4–2 A | Inst. release: 42 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1CA20-0DA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1DA20-0DA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 2.2–3.2 A | Inst. release: 65 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1EA20-0DA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 2.8–4 A | Inst. release: 82 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1FA20-0DA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 3.5–5 A | Inst. release: 104 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1GA20-0DA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1HA20-0DA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1JA20-0DA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1CA10-0BA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: no aux. switch, -50 °C version | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1GA10-0BA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: no aux. switch, -50 °C version | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1HA10-0BA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: no aux. switch, -50 °C version | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1JA10-0BA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: no aux. switch, -50 °C version | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-4AA10-0BA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch, -50 °C version | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-0AA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 0.11–0.16 A | Inst. release: 3.3 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-0BA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 0.14–0.2 A | Inst. release: 4.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-0CA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 0.18–0.25 A | Inst. release: 5.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-0DA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 0.22–0.32 A | Inst. release: 6.5 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-0EA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 0.28–0.4 A | Inst. release: 8.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-0FA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 0.35–0.5 A | Inst. release: 10 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-0GA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 0.45–0.63 A | Inst. release: 13 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-0HA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 0.55–0.8 A | Inst. release: 16 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-0JA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 0.7–1 A | Inst. release: 21 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-0KA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 0.9–1.25 A | Inst. release: 26 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-1AA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 1.1–1.6 A | Inst. release: 33 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-1BA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 1.4–2 A | Inst. release: 42 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-1CA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-1DA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 2.2–3.2 A | Inst. release: 65 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-1EA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 2.8–4 A | Inst. release: 82 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-1FA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 3.5–5 A | Inst. release: 104 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-1GA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-1HA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-1JA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-1KA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 9–12.5 A | Inst. release: 260 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-4AA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-4AA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-4BA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 13–20 A | Inst. release: 325 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-4BA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 13–20 A | Inst. release: 325 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-4CA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 16–22 A | Inst. release: 364 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-4CA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 16–22 A | Inst. release: 364 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-4DA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 18–25 A | Inst. release: 400 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-4DA20\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 18–25 A | Inst. release: 400 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-4AA20-0DA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-4BA20-0DA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 13–20 A | Inst. release: 325 A | Icu 400 V: 55 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-4BA10-0BA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 13–20 A | Inst. release: 325 A | Icu 400 V: 55 kA | Version: no aux. switch, -50 °C version | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2431-4SA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S2 | Setting range: 9.5–14 A | Inst. release: 328 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2431-4TA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S2 | Setting range: 12–17 A | Inst. release: 410 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2431-4BA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S2 | Setting range: 14–20 A | Inst. release: 410 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2431-4DA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S2 | Setting range: 18–25 A | Inst. release: 512 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2431-4EA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S2 | Setting range: 22–32 A | Inst. release: 656 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2431-4PA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S2 | Setting range: 28–36 A | Inst. release: 820 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2431-4UA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S2 | Setting range: 32–40 A | Inst. release: 820 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2431-4VA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S2 | Setting range: 35–45 A | Inst. release: 922 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2431-4WA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S2 | Setting range: 42–52 A | Inst. release: 1 025 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2431-4XA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S2 | Setting range: 49–59 A | Inst. release: 1 040 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2431-4JA10\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S2 | Setting range: 54–65 A | Inst. release: 1 040 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2431-4EA10-0BA0\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S2 | Setting range: 22–32 A | Inst. release: 656 A | Icu 400 V: 65 kA | Version: no aux. switch, -50 °C version | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0AA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.11–0.16 A | Inst. release: 3.3 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0BA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.14–0.2 A | Inst. release: 4.2 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0CA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.18–0.25 A | Inst. release: 5.2 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0DA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.22–0.32 A | Inst. release: 6.5 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0EA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.28–0.4 A | Inst. release: 8.2 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0FA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.35–0.5 A | Inst. release: 10 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0GA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.45–0.63 A | Inst. release: 13 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0HA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.55–0.8 A | Inst. release: 16 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0JA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.7–1 A | Inst. release: 21 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-0KA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 0.9–1.25 A | Inst. release: 26 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1AA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 1.1–1.6 A | Inst. release: 33 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1BA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 1.4–2 A | Inst. release: 42 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1CA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1DA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 2.2–3.2 A | Inst. release: 65 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1EA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 2.8–4 A | Inst. release: 82 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1FA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 3.5–5 A | Inst. release: 104 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1GA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1HA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1JA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-1KA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 9–12.5 A | Inst. release: 260 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2411-4AA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S00 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-4AA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-4BA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 13–20 A | Inst. release: 325 A | Icu 400 V: 55 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-4CA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 16–22 A | Inst. release: 364 A | Icu 400 V: 55 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3RV2421-4DA15\u003c\/td\u003e\n\u003ctd\u003e\u003c\/td\u003e\n\u003ctd\u003eSize: S0 | Setting range: 18–25 A | Inst. release: 400 A | Icu 400 V: 55 kA | Version: 1 NO + 1 NC | Connection: Screw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\u003c\/table\u003e","brand":"Siemens","offers":[{"title":"Default Title","offer_id":67534399766818,"sku":"3RV2411-0AA10","price":0.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/1021\/0744\/7586\/files\/siemens-sirius-3rv24-circuit-breakers-transformer-protection.jpg?v=1792131833","url":"https:\/\/prosourcemro.com\/products\/siemens-sirius-3rv24-circuit-breakers-transformer-protection","provider":"ProSource MRO","version":"1.0","type":"link"}