SIRIUS 3RV24 circuit breakers protect transformers with high inrush currents, with raised instantaneous release settings in sizes S00 to S2.

Key features

  • Instantaneous release set approx. 20x In to ride through transformer inrush
  • Class 10 adjustable thermal overload release, 0.11 A to 65 A
  • Short-circuit breaking capacity up to 100 kA at 400 V AC
  • Versions without phase-failure detection for 1-, 2- and 3-phase loads (-0DA0)
  • Screw or spring-loaded terminals; versions with transverse auxiliary switch 1 NO + 1 NC

Specifications

Product line SIRIUS 3RV2
Class 10
Application Transformers with high inrush current
Brand Siemens
Catalog section IC 10 ch. 7 Protection equipment
Category Motor Starter Protectors
Poles 3
Rated frequency 50/60 Hz
Mounting DIN rail or screw fixing
Source Siemens Catalog IC 10 · 2026, p. 7/38-7/41
3RV2411-0AA10 Size: S00 | Setting range: 0.11–0.16 A | Inst. release: 3.3 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0AA20 Size: S00 | Setting range: 0.11–0.16 A | Inst. release: 3.3 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0BA10 Size: S00 | Setting range: 0.14–0.2 A | Inst. release: 4.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0BA20 Size: S00 | Setting range: 0.14–0.2 A | Inst. release: 4.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0CA10 Size: S00 | Setting range: 0.18–0.25 A | Inst. release: 5.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0CA20 Size: S00 | Setting range: 0.18–0.25 A | Inst. release: 5.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0DA10 Size: S00 | Setting range: 0.22–0.32 A | Inst. release: 6.5 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0DA20 Size: S00 | Setting range: 0.22–0.32 A | Inst. release: 6.5 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0EA10 Size: S00 | Setting range: 0.28–0.4 A | Inst. release: 8.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0EA20 Size: S00 | Setting range: 0.28–0.4 A | Inst. release: 8.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0FA10 Size: S00 | Setting range: 0.35–0.5 A | Inst. release: 10 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0FA20 Size: S00 | Setting range: 0.35–0.5 A | Inst. release: 10 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0GA10 Size: S00 | Setting range: 0.45–0.63 A | Inst. release: 13 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0GA20 Size: S00 | Setting range: 0.45–0.63 A | Inst. release: 13 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0HA10 Size: S00 | Setting range: 0.55–0.8 A | Inst. release: 16 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0HA20 Size: S00 | Setting range: 0.55–0.8 A | Inst. release: 16 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0JA10 Size: S00 | Setting range: 0.7–1 A | Inst. release: 21 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0JA20 Size: S00 | Setting range: 0.7–1 A | Inst. release: 21 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0KA10 Size: S00 | Setting range: 0.9–1.25 A | Inst. release: 26 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0KA20 Size: S00 | Setting range: 0.9–1.25 A | Inst. release: 26 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1AA10 Size: S00 | Setting range: 1.1–1.6 A | Inst. release: 33 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1AA20 Size: S00 | Setting range: 1.1–1.6 A | Inst. release: 33 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1BA10 Size: S00 | Setting range: 1.4–2 A | Inst. release: 42 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1BA20 Size: S00 | Setting range: 1.4–2 A | Inst. release: 42 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1CA10 Size: S00 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1CA20 Size: S00 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1DA10 Size: S00 | Setting range: 2.2–3.2 A | Inst. release: 65 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1DA20 Size: S00 | Setting range: 2.2–3.2 A | Inst. release: 65 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1EA10 Size: S00 | Setting range: 2.8–4 A | Inst. release: 82 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1EA20 Size: S00 | Setting range: 2.8–4 A | Inst. release: 82 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1FA10 Size: S00 | Setting range: 3.5–5 A | Inst. release: 104 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1FA20 Size: S00 | Setting range: 3.5–5 A | Inst. release: 104 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1GA10 Size: S00 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1GA20 Size: S00 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1HA10 Size: S00 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1HA20 Size: S00 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1JA10 Size: S00 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1JA20 Size: S00 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1KA10 Size: S00 | Setting range: 9–12.5 A | Inst. release: 260 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1KA20 Size: S00 | Setting range: 9–12.5 A | Inst. release: 260 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-4AA10 Size: S00 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Screw
3RV2411-4AA20 Size: S00 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0EA20-0DA0 Size: S00 | Setting range: 0.28–0.4 A | Inst. release: 8.2 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1AA20-0DA0 Size: S00 | Setting range: 1.1–1.6 A | Inst. release: 33 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1BA20-0DA0 Size: S00 | Setting range: 1.4–2 A | Inst. release: 42 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1CA20-0DA0 Size: S00 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1DA20-0DA0 Size: S00 | Setting range: 2.2–3.2 A | Inst. release: 65 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1EA20-0DA0 Size: S00 | Setting range: 2.8–4 A | Inst. release: 82 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1FA20-0DA0 Size: S00 | Setting range: 3.5–5 A | Inst. release: 104 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1GA20-0DA0 Size: S00 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1HA20-0DA0 Size: S00 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1JA20-0DA0 Size: S00 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1CA10-0BA0 Size: S00 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: no aux. switch, -50 °C version | Connection: Screw
3RV2411-1GA10-0BA0 Size: S00 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: no aux. switch, -50 °C version | Connection: Screw
3RV2411-1HA10-0BA0 Size: S00 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: no aux. switch, -50 °C version | Connection: Screw
3RV2411-1JA10-0BA0 Size: S00 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: no aux. switch, -50 °C version | Connection: Screw
3RV2411-4AA10-0BA0 Size: S00 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch, -50 °C version | Connection: Screw
3RV2421-0AA10 Size: S0 | Setting range: 0.11–0.16 A | Inst. release: 3.3 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0BA10 Size: S0 | Setting range: 0.14–0.2 A | Inst. release: 4.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0CA10 Size: S0 | Setting range: 0.18–0.25 A | Inst. release: 5.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0DA10 Size: S0 | Setting range: 0.22–0.32 A | Inst. release: 6.5 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0EA10 Size: S0 | Setting range: 0.28–0.4 A | Inst. release: 8.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0FA10 Size: S0 | Setting range: 0.35–0.5 A | Inst. release: 10 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0GA10 Size: S0 | Setting range: 0.45–0.63 A | Inst. release: 13 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0HA10 Size: S0 | Setting range: 0.55–0.8 A | Inst. release: 16 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0JA10 Size: S0 | Setting range: 0.7–1 A | Inst. release: 21 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0KA10 Size: S0 | Setting range: 0.9–1.25 A | Inst. release: 26 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1AA10 Size: S0 | Setting range: 1.1–1.6 A | Inst. release: 33 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1BA10 Size: S0 | Setting range: 1.4–2 A | Inst. release: 42 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1CA10 Size: S0 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1DA10 Size: S0 | Setting range: 2.2–3.2 A | Inst. release: 65 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1EA10 Size: S0 | Setting range: 2.8–4 A | Inst. release: 82 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1FA10 Size: S0 | Setting range: 3.5–5 A | Inst. release: 104 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1GA10 Size: S0 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1HA10 Size: S0 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1JA10 Size: S0 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1KA10 Size: S0 | Setting range: 9–12.5 A | Inst. release: 260 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-4AA10 Size: S0 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Screw
3RV2421-4AA20 Size: S0 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2421-4BA10 Size: S0 | Setting range: 13–20 A | Inst. release: 325 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Screw
3RV2421-4BA20 Size: S0 | Setting range: 13–20 A | Inst. release: 325 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2421-4CA10 Size: S0 | Setting range: 16–22 A | Inst. release: 364 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Screw
3RV2421-4CA20 Size: S0 | Setting range: 16–22 A | Inst. release: 364 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2421-4DA10 Size: S0 | Setting range: 18–25 A | Inst. release: 400 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Screw
3RV2421-4DA20 Size: S0 | Setting range: 18–25 A | Inst. release: 400 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2421-4AA20-0DA0 Size: S0 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2421-4BA20-0DA0 Size: S0 | Setting range: 13–20 A | Inst. release: 325 A | Icu 400 V: 55 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2421-4BA10-0BA0 Size: S0 | Setting range: 13–20 A | Inst. release: 325 A | Icu 400 V: 55 kA | Version: no aux. switch, -50 °C version | Connection: Screw
3RV2431-4SA10 Size: S2 | Setting range: 9.5–14 A | Inst. release: 328 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4TA10 Size: S2 | Setting range: 12–17 A | Inst. release: 410 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4BA10 Size: S2 | Setting range: 14–20 A | Inst. release: 410 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4DA10 Size: S2 | Setting range: 18–25 A | Inst. release: 512 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4EA10 Size: S2 | Setting range: 22–32 A | Inst. release: 656 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4PA10 Size: S2 | Setting range: 28–36 A | Inst. release: 820 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4UA10 Size: S2 | Setting range: 32–40 A | Inst. release: 820 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4VA10 Size: S2 | Setting range: 35–45 A | Inst. release: 922 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4WA10 Size: S2 | Setting range: 42–52 A | Inst. release: 1 025 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4XA10 Size: S2 | Setting range: 49–59 A | Inst. release: 1 040 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4JA10 Size: S2 | Setting range: 54–65 A | Inst. release: 1 040 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4EA10-0BA0 Size: S2 | Setting range: 22–32 A | Inst. release: 656 A | Icu 400 V: 65 kA | Version: no aux. switch, -50 °C version | Connection: Screw
3RV2411-0AA15 Size: S00 | Setting range: 0.11–0.16 A | Inst. release: 3.3 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0BA15 Size: S00 | Setting range: 0.14–0.2 A | Inst. release: 4.2 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0CA15 Size: S00 | Setting range: 0.18–0.25 A | Inst. release: 5.2 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0DA15 Size: S00 | Setting range: 0.22–0.32 A | Inst. release: 6.5 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0EA15 Size: S00 | Setting range: 0.28–0.4 A | Inst. release: 8.2 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0FA15 Size: S00 | Setting range: 0.35–0.5 A | Inst. release: 10 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0GA15 Size: S00 | Setting range: 0.45–0.63 A | Inst. release: 13 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0HA15 Size: S00 | Setting range: 0.55–0.8 A | Inst. release: 16 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0JA15 Size: S00 | Setting range: 0.7–1 A | Inst. release: 21 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0KA15 Size: S00 | Setting range: 0.9–1.25 A | Inst. release: 26 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1AA15 Size: S00 | Setting range: 1.1–1.6 A | Inst. release: 33 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1BA15 Size: S00 | Setting range: 1.4–2 A | Inst. release: 42 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1CA15 Size: S00 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1DA15 Size: S00 | Setting range: 2.2–3.2 A | Inst. release: 65 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1EA15 Size: S00 | Setting range: 2.8–4 A | Inst. release: 82 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1FA15 Size: S00 | Setting range: 3.5–5 A | Inst. release: 104 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1GA15 Size: S00 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1HA15 Size: S00 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1JA15 Size: S00 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1KA15 Size: S00 | Setting range: 9–12.5 A | Inst. release: 260 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-4AA15 Size: S00 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2421-4AA15 Size: S0 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2421-4BA15 Size: S0 | Setting range: 13–20 A | Inst. release: 325 A | Icu 400 V: 55 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2421-4CA15 Size: S0 | Setting range: 16–22 A | Inst. release: 364 A | Icu 400 V: 55 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2421-4DA15 Size: S0 | Setting range: 18–25 A | Inst. release: 400 A | Icu 400 V: 55 kA | Version: 1 NO + 1 NC | Connection: Screw
Motor Starter ProtectorsSiemens
125 product codes available in this family
Sourced direct from KoreaExport-ready supplyCompetitive pricing

Need a different model, or a part not listed here? Send us your parts list →

Siemens SIRIUS 3RV24 Circuit Breakers for Transformer Protection

Brand Siemens·Motor Starter Protectors

Available part numbers (125)

3RV2411-0AA10, 3RV2411-0AA20, 3RV2411-0BA10, 3RV2411-0BA20, 3RV2411-0CA10, 3RV2411-0CA20, 3RV2411-0DA10, 3RV2411-0DA20, 3RV2411-0EA10, 3RV2411-0EA20 + 115 more — see full table ↓

How to order

Send the Siemens part numbers and quantities through our RFQ form or to info@prosourcemro.com. We confirm price, availability and lead time within 1 business day — no account needed.

RFQ List 0 →
View full details
Product codes & specifications
0 selected
RFQ List (0)
Product codeSpec
3RV2411-0AA10Size: S00 | Setting range: 0.11–0.16 A | Inst. release: 3.3 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0AA20Size: S00 | Setting range: 0.11–0.16 A | Inst. release: 3.3 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0BA10Size: S00 | Setting range: 0.14–0.2 A | Inst. release: 4.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0BA20Size: S00 | Setting range: 0.14–0.2 A | Inst. release: 4.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0CA10Size: S00 | Setting range: 0.18–0.25 A | Inst. release: 5.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0CA20Size: S00 | Setting range: 0.18–0.25 A | Inst. release: 5.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0DA10Size: S00 | Setting range: 0.22–0.32 A | Inst. release: 6.5 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0DA20Size: S00 | Setting range: 0.22–0.32 A | Inst. release: 6.5 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0EA10Size: S00 | Setting range: 0.28–0.4 A | Inst. release: 8.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0EA20Size: S00 | Setting range: 0.28–0.4 A | Inst. release: 8.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0FA10Size: S00 | Setting range: 0.35–0.5 A | Inst. release: 10 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0FA20Size: S00 | Setting range: 0.35–0.5 A | Inst. release: 10 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0GA10Size: S00 | Setting range: 0.45–0.63 A | Inst. release: 13 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0GA20Size: S00 | Setting range: 0.45–0.63 A | Inst. release: 13 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0HA10Size: S00 | Setting range: 0.55–0.8 A | Inst. release: 16 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0HA20Size: S00 | Setting range: 0.55–0.8 A | Inst. release: 16 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0JA10Size: S00 | Setting range: 0.7–1 A | Inst. release: 21 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0JA20Size: S00 | Setting range: 0.7–1 A | Inst. release: 21 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0KA10Size: S00 | Setting range: 0.9–1.25 A | Inst. release: 26 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-0KA20Size: S00 | Setting range: 0.9–1.25 A | Inst. release: 26 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1AA10Size: S00 | Setting range: 1.1–1.6 A | Inst. release: 33 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1AA20Size: S00 | Setting range: 1.1–1.6 A | Inst. release: 33 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1BA10Size: S00 | Setting range: 1.4–2 A | Inst. release: 42 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1BA20Size: S00 | Setting range: 1.4–2 A | Inst. release: 42 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1CA10Size: S00 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1CA20Size: S00 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1DA10Size: S00 | Setting range: 2.2–3.2 A | Inst. release: 65 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1DA20Size: S00 | Setting range: 2.2–3.2 A | Inst. release: 65 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1EA10Size: S00 | Setting range: 2.8–4 A | Inst. release: 82 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1EA20Size: S00 | Setting range: 2.8–4 A | Inst. release: 82 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1FA10Size: S00 | Setting range: 3.5–5 A | Inst. release: 104 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1FA20Size: S00 | Setting range: 3.5–5 A | Inst. release: 104 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1GA10Size: S00 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1GA20Size: S00 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1HA10Size: S00 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1HA20Size: S00 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1JA10Size: S00 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1JA20Size: S00 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-1KA10Size: S00 | Setting range: 9–12.5 A | Inst. release: 260 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2411-1KA20Size: S00 | Setting range: 9–12.5 A | Inst. release: 260 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-4AA10Size: S00 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Screw
3RV2411-4AA20Size: S00 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2411-0EA20-0DA0Size: S00 | Setting range: 0.28–0.4 A | Inst. release: 8.2 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1AA20-0DA0Size: S00 | Setting range: 1.1–1.6 A | Inst. release: 33 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1BA20-0DA0Size: S00 | Setting range: 1.4–2 A | Inst. release: 42 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1CA20-0DA0Size: S00 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1DA20-0DA0Size: S00 | Setting range: 2.2–3.2 A | Inst. release: 65 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1EA20-0DA0Size: S00 | Setting range: 2.8–4 A | Inst. release: 82 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1FA20-0DA0Size: S00 | Setting range: 3.5–5 A | Inst. release: 104 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1GA20-0DA0Size: S00 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1HA20-0DA0Size: S00 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1JA20-0DA0Size: S00 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2411-1CA10-0BA0Size: S00 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: no aux. switch, -50 °C version | Connection: Screw
3RV2411-1GA10-0BA0Size: S00 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: no aux. switch, -50 °C version | Connection: Screw
3RV2411-1HA10-0BA0Size: S00 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: no aux. switch, -50 °C version | Connection: Screw
3RV2411-1JA10-0BA0Size: S00 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: no aux. switch, -50 °C version | Connection: Screw
3RV2411-4AA10-0BA0Size: S00 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch, -50 °C version | Connection: Screw
3RV2421-0AA10Size: S0 | Setting range: 0.11–0.16 A | Inst. release: 3.3 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0BA10Size: S0 | Setting range: 0.14–0.2 A | Inst. release: 4.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0CA10Size: S0 | Setting range: 0.18–0.25 A | Inst. release: 5.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0DA10Size: S0 | Setting range: 0.22–0.32 A | Inst. release: 6.5 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0EA10Size: S0 | Setting range: 0.28–0.4 A | Inst. release: 8.2 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0FA10Size: S0 | Setting range: 0.35–0.5 A | Inst. release: 10 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0GA10Size: S0 | Setting range: 0.45–0.63 A | Inst. release: 13 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0HA10Size: S0 | Setting range: 0.55–0.8 A | Inst. release: 16 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0JA10Size: S0 | Setting range: 0.7–1 A | Inst. release: 21 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-0KA10Size: S0 | Setting range: 0.9–1.25 A | Inst. release: 26 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1AA10Size: S0 | Setting range: 1.1–1.6 A | Inst. release: 33 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1BA10Size: S0 | Setting range: 1.4–2 A | Inst. release: 42 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1CA10Size: S0 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1DA10Size: S0 | Setting range: 2.2–3.2 A | Inst. release: 65 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1EA10Size: S0 | Setting range: 2.8–4 A | Inst. release: 82 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1FA10Size: S0 | Setting range: 3.5–5 A | Inst. release: 104 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1GA10Size: S0 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1HA10Size: S0 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1JA10Size: S0 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-1KA10Size: S0 | Setting range: 9–12.5 A | Inst. release: 260 A | Icu 400 V: 100 kA | Version: no aux. switch | Connection: Screw
3RV2421-4AA10Size: S0 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Screw
3RV2421-4AA20Size: S0 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2421-4BA10Size: S0 | Setting range: 13–20 A | Inst. release: 325 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Screw
3RV2421-4BA20Size: S0 | Setting range: 13–20 A | Inst. release: 325 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2421-4CA10Size: S0 | Setting range: 16–22 A | Inst. release: 364 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Screw
3RV2421-4CA20Size: S0 | Setting range: 16–22 A | Inst. release: 364 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2421-4DA10Size: S0 | Setting range: 18–25 A | Inst. release: 400 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Screw
3RV2421-4DA20Size: S0 | Setting range: 18–25 A | Inst. release: 400 A | Icu 400 V: 55 kA | Version: no aux. switch | Connection: Spring-loaded
3RV2421-4AA20-0DA0Size: S0 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2421-4BA20-0DA0Size: S0 | Setting range: 13–20 A | Inst. release: 325 A | Icu 400 V: 55 kA | Version: no aux. switch, no phase-failure det. | Connection: Spring-loaded
3RV2421-4BA10-0BA0Size: S0 | Setting range: 13–20 A | Inst. release: 325 A | Icu 400 V: 55 kA | Version: no aux. switch, -50 °C version | Connection: Screw
3RV2431-4SA10Size: S2 | Setting range: 9.5–14 A | Inst. release: 328 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4TA10Size: S2 | Setting range: 12–17 A | Inst. release: 410 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4BA10Size: S2 | Setting range: 14–20 A | Inst. release: 410 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4DA10Size: S2 | Setting range: 18–25 A | Inst. release: 512 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4EA10Size: S2 | Setting range: 22–32 A | Inst. release: 656 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4PA10Size: S2 | Setting range: 28–36 A | Inst. release: 820 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4UA10Size: S2 | Setting range: 32–40 A | Inst. release: 820 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4VA10Size: S2 | Setting range: 35–45 A | Inst. release: 922 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4WA10Size: S2 | Setting range: 42–52 A | Inst. release: 1 025 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4XA10Size: S2 | Setting range: 49–59 A | Inst. release: 1 040 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4JA10Size: S2 | Setting range: 54–65 A | Inst. release: 1 040 A | Icu 400 V: 65 kA | Version: no aux. switch | Connection: Screw
3RV2431-4EA10-0BA0Size: S2 | Setting range: 22–32 A | Inst. release: 656 A | Icu 400 V: 65 kA | Version: no aux. switch, -50 °C version | Connection: Screw
3RV2411-0AA15Size: S00 | Setting range: 0.11–0.16 A | Inst. release: 3.3 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0BA15Size: S00 | Setting range: 0.14–0.2 A | Inst. release: 4.2 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0CA15Size: S00 | Setting range: 0.18–0.25 A | Inst. release: 5.2 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0DA15Size: S00 | Setting range: 0.22–0.32 A | Inst. release: 6.5 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0EA15Size: S00 | Setting range: 0.28–0.4 A | Inst. release: 8.2 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0FA15Size: S00 | Setting range: 0.35–0.5 A | Inst. release: 10 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0GA15Size: S00 | Setting range: 0.45–0.63 A | Inst. release: 13 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0HA15Size: S00 | Setting range: 0.55–0.8 A | Inst. release: 16 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0JA15Size: S00 | Setting range: 0.7–1 A | Inst. release: 21 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-0KA15Size: S00 | Setting range: 0.9–1.25 A | Inst. release: 26 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1AA15Size: S00 | Setting range: 1.1–1.6 A | Inst. release: 33 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1BA15Size: S00 | Setting range: 1.4–2 A | Inst. release: 42 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1CA15Size: S00 | Setting range: 1.8–2.5 A | Inst. release: 52 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1DA15Size: S00 | Setting range: 2.2–3.2 A | Inst. release: 65 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1EA15Size: S00 | Setting range: 2.8–4 A | Inst. release: 82 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1FA15Size: S00 | Setting range: 3.5–5 A | Inst. release: 104 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1GA15Size: S00 | Setting range: 4.5–6.3 A | Inst. release: 130 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1HA15Size: S00 | Setting range: 5.5–8 A | Inst. release: 163 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1JA15Size: S00 | Setting range: 7–10 A | Inst. release: 208 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-1KA15Size: S00 | Setting range: 9–12.5 A | Inst. release: 260 A | Icu 400 V: 100 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2411-4AA15Size: S00 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2421-4AA15Size: S0 | Setting range: 10–16 A | Inst. release: 286 A | Icu 400 V: 55 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2421-4BA15Size: S0 | Setting range: 13–20 A | Inst. release: 325 A | Icu 400 V: 55 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2421-4CA15Size: S0 | Setting range: 16–22 A | Inst. release: 364 A | Icu 400 V: 55 kA | Version: 1 NO + 1 NC | Connection: Screw
3RV2421-4DA15Size: S0 | Setting range: 18–25 A | Inst. release: 400 A | Icu 400 V: 55 kA | Version: 1 NO + 1 NC | Connection: Screw