Converter Units
MITSUBISHI ELECTRIC
[MITSUBISHI ELECTRIC] — FR-HC2 High Power Factor Converter (3-Phase 400V, 7.5-560kW)
Family ID: MEL-FRHC2-400V
FR-HC2 high power factor converter, 3-phase 400V, 7.5-560kW. Harmonic suppression (equivalent-capacity conversion coefficient K5=0), standard power regeneration (100% continuous / 150% 60s), input power factor 0.99+, up to 10 inverters connectable.
11 product codes available in this family
Product Codes & Specifications
| Product Code | Description | Brand | Spec | ||
|---|---|---|---|---|---|
| FR-HC2-H7.5K | FR-HC2 high power factor converter 7.5kW, 400V class, harmonic suppression + power regeneration | MITSUBISHI ELECTRIC | Applicable Inverter Capacity: 7.5 kW · Rated DC Output Capacity: 11.0 kW · Rated Input Voltage: 3-ph 380-460V 50/60Hz · Rated Input Current: 17 A · Overload: 150% 60s · Permissible Voltage Fluctuation: 323-506V 50/60Hz · Frequency Fluctuation: +/-5% · Input Power Factor: 0.99 or more (at 100% load) · Power Supply Capacity: 14 kVA · Power Regeneration: 100% torque continuous / 150% torque 60s max · Harmonic Suppression: equivalent-capacity conversion coefficient K5=0 · Multi-inverter: up to 10 units connectable · Enclosure: Closed IP20 · Cooling: Forced-air · Mass (converter): 9 kg · Included Peripherals: Reactor 1 (FR-HCL21-H7.5K), Reactor 2 (FR-HCL22-H7.5K), Outside Box (FR-HCB2-H7.5K) | ||
| FR-HC2-H15K | FR-HC2 high power factor converter 15kW, 400V class, harmonic suppression + power regeneration | MITSUBISHI ELECTRIC | Applicable Inverter Capacity: 15 kW · Rated DC Output Capacity: 20.2 kW · Rated Input Voltage: 3-ph 380-460V 50/60Hz · Rated Input Current: 31 A · Overload: 150% 60s · Permissible Voltage Fluctuation: 323-506V 50/60Hz · Frequency Fluctuation: +/-5% · Input Power Factor: 0.99 or more (at 100% load) · Power Supply Capacity: 26 kVA · Power Regeneration: 100% torque continuous / 150% torque 60s max · Harmonic Suppression: equivalent-capacity conversion coefficient K5=0 · Multi-inverter: up to 10 units connectable · Enclosure: Closed IP20 · Cooling: Forced-air · Mass (converter): 9 kg · Included Peripherals: Reactor 1 (FR-HCL21-H15K), Reactor 2 (FR-HCL22-H15K), Outside Box (FR-HCB2-H15K) | ||
| FR-HC2-H30K | FR-HC2 high power factor converter 30kW, 400V class, harmonic suppression + power regeneration | MITSUBISHI ELECTRIC | Applicable Inverter Capacity: 30 kW · Rated DC Output Capacity: 37 kW · Rated Input Voltage: 3-ph 380-460V 50/60Hz · Rated Input Current: 57 A · Overload: 150% 60s · Permissible Voltage Fluctuation: 323-506V 50/60Hz · Frequency Fluctuation: +/-5% · Input Power Factor: 0.99 or more (at 100% load) · Power Supply Capacity: 47 kVA · Power Regeneration: 100% torque continuous / 150% torque 60s max · Harmonic Suppression: equivalent-capacity conversion coefficient K5=0 · Multi-inverter: up to 10 units connectable · Enclosure: Open IP00 · Cooling: Forced-air · Mass (converter): 26 kg · Included Peripherals: Reactor 1 (FR-HCL21-H30K), Reactor 2 (FR-HCL22-H30K), Outside Box (FR-HCB2-H30K) | ||
| FR-HC2-H55K | FR-HC2 high power factor converter 55kW, 400V class, harmonic suppression + power regeneration | MITSUBISHI ELECTRIC | Applicable Inverter Capacity: 55 kW · Rated DC Output Capacity: 73 kW · Rated Input Voltage: 3-ph 380-460V 50/60Hz · Rated Input Current: 110 A · Overload: 150% 60s · Permissible Voltage Fluctuation: 323-506V 50/60Hz · Frequency Fluctuation: +/-5% · Input Power Factor: 0.99 or more (at 100% load) · Power Supply Capacity: 90 kVA · Power Regeneration: 100% torque continuous / 150% torque 60s max · Harmonic Suppression: equivalent-capacity conversion coefficient K5=0 · Multi-inverter: up to 10 units connectable · Enclosure: Open IP00 · Cooling: Forced-air · Mass (converter): 43 kg · Included Peripherals: Reactor 1 (FR-HCL21-H55K), Reactor 2 (FR-HCL22-H55K), Outside Box (FR-HCB2-H55K) | ||
| FR-HC2-H75K | FR-HC2 high power factor converter 75kW, 400V class, harmonic suppression + power regeneration | MITSUBISHI ELECTRIC | Applicable Inverter Capacity: 75 kW · Rated DC Output Capacity: 92 kW · Rated Input Voltage: 3-ph 380-460V 50/60Hz · Rated Input Current: 139 A · Overload: 150% 60s · Permissible Voltage Fluctuation: 323-460V 50/60Hz · Frequency Fluctuation: +/-5% · Input Power Factor: 0.99 or more (at 100% load) · Power Supply Capacity: 113 kVA · Power Regeneration: 100% torque continuous / 150% torque 60s max · Harmonic Suppression: equivalent-capacity conversion coefficient K5=0 · Multi-inverter: up to 10 units connectable · Enclosure: Open IP00 · Cooling: Forced-air · Mass (converter): 37 kg · Included Peripherals: Reactor 1 (FR-HCL21-H75K), Reactor 2 (FR-HCL22-H75K), Outside Box (FR-HCB2-H75K) | ||
| FR-HC2-H110K | FR-HC2 high power factor converter 110kW, 400V class, harmonic suppression + power regeneration | MITSUBISHI ELECTRIC | Applicable Inverter Capacity: 110 kW · Rated DC Output Capacity: 135 kW · Rated Input Voltage: 3-ph 380-460V 50/60Hz · Rated Input Current: 203 A · Overload: 150% 60s · Permissible Voltage Fluctuation: 323-460V 50/60Hz · Frequency Fluctuation: +/-5% · Input Power Factor: 0.99 or more (at 100% load) · Power Supply Capacity: 165 kVA · Power Regeneration: 100% torque continuous / 150% torque 60s max · Harmonic Suppression: equivalent-capacity conversion coefficient K5=0 · Multi-inverter: up to 10 units connectable · Enclosure: Open IP00 · Cooling: Forced-air · Mass (converter): 56 kg · Included Peripherals: Reactor 1 (FR-HCL21-H110K), Reactor 2 (FR-HCL22-H110K), Outside Box (FR-HCB2-H110K) | ||
| FR-HC2-H160K | FR-HC2 high power factor converter 160kW, 400V class, harmonic suppression + power regeneration | MITSUBISHI ELECTRIC | Applicable Inverter Capacity: 160 kW · Rated DC Output Capacity: 192 kW · Rated Input Voltage: 3-ph 380-460V 50/60Hz · Rated Input Current: 290 A · Overload: 150% 60s · Permissible Voltage Fluctuation: 323-460V 50/60Hz · Frequency Fluctuation: +/-5% · Input Power Factor: 0.99 or more (at 100% load) · Power Supply Capacity: 235 kVA · Power Regeneration: 100% torque continuous / 150% torque 60s max · Harmonic Suppression: equivalent-capacity conversion coefficient K5=0 · Multi-inverter: up to 10 units connectable · Enclosure: Open IP00 · Cooling: Forced-air · Mass (converter): 120 kg · Included Peripherals: Reactor 1 (FR-HCL21-H160K), Reactor 2 (FR-HCL22-H160K), Outside Box (FR-HCB2-H160K) | ||
| FR-HC2-H220K | FR-HC2 high power factor converter 220kW, 400V class, harmonic suppression + power regeneration | MITSUBISHI ELECTRIC | Applicable Inverter Capacity: 220 kW · Rated DC Output Capacity: 264 kW · Rated Input Voltage: 3-ph 380-460V 50/60Hz · Rated Input Current: 397 A · Overload: 150% 60s · Permissible Voltage Fluctuation: 323-460V 50/60Hz · Frequency Fluctuation: +/-5% · Input Power Factor: 0.99 or more (at 100% load) · Power Supply Capacity: 322 kVA · Power Regeneration: 100% torque continuous / 150% torque 60s max · Harmonic Suppression: equivalent-capacity conversion coefficient K5=0 · Multi-inverter: up to 10 units connectable · Enclosure: Open IP00 · Cooling: Forced-air · Mass (converter): 120 kg · Included Peripherals: Reactor 1 (FR-HCL21-H220K), Reactor 2 (FR-HCL22-H220K), Outside Box (FR-HCB2-H220K) | ||
| FR-HC2-H280K | FR-HC2 high power factor converter 280kW, 400V class, harmonic suppression + power regeneration | MITSUBISHI ELECTRIC | Applicable Inverter Capacity: 280 kW · Rated DC Output Capacity: 336 kW · Rated Input Voltage: 3-ph 380-460V 50/60Hz · Rated Input Current: 506 A · Overload: 150% 60s · Permissible Voltage Fluctuation: 323-460V 50/60Hz · Frequency Fluctuation: +/-5% · Input Power Factor: 0.99 or more (at 100% load) · Power Supply Capacity: 410 kVA · Power Regeneration: 100% torque continuous / 150% torque 60s max · Harmonic Suppression: equivalent-capacity conversion coefficient K5=0 · Multi-inverter: up to 10 units connectable · Enclosure: Open IP00 · Cooling: Forced-air · Mass (converter): 160 kg · Included Peripherals: Reactor 1 (FR-HCL21-H280K), Reactor 2 (FR-HCL22-H280K), Filter Capacitor (FR-HCC2-H280K), Inrush Resistor (FR-HCR2-H280K), MC Kit (FR-HCM2-H280K) | ||
| FR-HC2-H400K | FR-HC2 high power factor converter 400kW, 400V class, harmonic suppression + power regeneration | MITSUBISHI ELECTRIC | Applicable Inverter Capacity: 400 kW · Rated DC Output Capacity: 476 kW · Rated Input Voltage: 3-ph 380-460V 50/60Hz · Rated Input Current: 716 A · Overload: 150% 60s · Permissible Voltage Fluctuation: 323-460V 50/60Hz · Frequency Fluctuation: +/-5% · Input Power Factor: 0.99 or more (at 100% load) · Power Supply Capacity: 580 kVA · Power Regeneration: 100% torque continuous / 150% torque 60s max · Harmonic Suppression: equivalent-capacity conversion coefficient K5=0 · Multi-inverter: up to 10 units connectable · Enclosure: Open IP00 · Cooling: Forced-air · Mass (converter): 250 kg · Included Peripherals: Reactor 1 (FR-HCL21-H400K), Reactor 2 (FR-HCL22-H400K), Filter Capacitor (FR-HCC2-H400K), Inrush Resistor (FR-HCR2-H400K), MC Kit (FR-HCM2-H400K) | ||
| FR-HC2-H560K | FR-HC2 high power factor converter 560kW, 400V class, harmonic suppression + power regeneration | MITSUBISHI ELECTRIC | Applicable Inverter Capacity: 560 kW · Rated DC Output Capacity: 660 kW · Rated Input Voltage: 3-ph 380-460V 50/60Hz · Rated Input Current: 993 A · Overload: 150% 60s · Permissible Voltage Fluctuation: 323-460V 50/60Hz · Frequency Fluctuation: +/-5% · Input Power Factor: 0.99 or more (at 100% load) · Power Supply Capacity: 804 kVA · Power Regeneration: 100% torque continuous / 150% torque 60s max · Harmonic Suppression: equivalent-capacity conversion coefficient K5=0 · Multi-inverter: up to 10 units connectable · Enclosure: Open IP00 · Cooling: Forced-air · Mass (converter): 250 kg · Included Peripherals: Reactor 1 (FR-HCL21-H560K), Reactor 2 (FR-HCL22-H560K), Filter Capacitor (FR-HCC2-H560K), Inrush Resistor (FR-HCR2-H560K), MC Kit (FR-HCM2-H560K) |