Skip to product information
1 of 1

LS Electric Susol UTS150 UL 489 MCCB (1.6-150 A)

LS Electric Susol UTS150 UL 489 MCCB (1.6-150 A)

LS Electric Susol UTS150 molded case circuit breakers are UL 489 listed for North American and export panels, covering 1.6-150 A with thermal-magnetic, electronic, switch and motor-protection versions.

Key features

  • UL 489 listed 150 AF breaker, 2P and 3P, up to 600 Vac
  • N, H and L interrupting classes up to 150 kA at 240 Vac
  • FTU, FMU, ATU thermal-magnetic and ETS23 electronic trip units
  • MCS molded case switch and MCP motor circuit protector (1.6-150 A, 3P) versions
  • HACR rated; DC rated up to 600 Vdc (3P in series)

Specifications

Frame size 150 AF
Rated insulation voltage (Ui) AC 750 V
Rated impulse voltage (Uimp) 8 kV
UL 489 interrupting rating (240/480/600 V) N 65/35/18 kA, H 100/65/35 kA, L 150/100/50 kA
DC rating (250 V 2P / 600 V 3P) N 35 kA, H 50 kA, L 65 kA
Dimensions (W x H x D) 105 x 165 x 87.5 mm (2P/3P)
Applications HACR
Standards UL 489, CSA C22.2 No.5, IEC 60947-2
Rated frequency AC 50/60 Hz
Source LS Electric Susol UL MCCB catalog C01081-17 (2026-07), p. 19-22
UTS150-H-FTU-40A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-40A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-40A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-40A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-40A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-40A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-40A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-40A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-40A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-40A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-40A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-40A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 3P
UTS150-H-FTU-50A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-50A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-50A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-50A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-50A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-50A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-50A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-50A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-50A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-50A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-50A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-50A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 3P
UTS150-H-FTU-60A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-60A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-60A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-60A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-60A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-60A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-60A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-60A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-60A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-60A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-60A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-60A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 3P
UTS150-H-FTU-70A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-70A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-70A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-70A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-70A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-70A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-70A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-70A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-70A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-70A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-70A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-70A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 3P
UTS150-H-FTU-80A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-80A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-80A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-80A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-80A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-80A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-80A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-80A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-80A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-80A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-80A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-80A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 3P
UTS150-H-FTU-90A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-90A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-90A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-90A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-90A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-90A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-90A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-90A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-90A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-90A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-90A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-90A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 3P
UTS150-H-FTU-100A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-100A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-100A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-100A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-100A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-100A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-100A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-100A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-100A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-100A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-100A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-100A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 3P
UTS150-H-FTU-125A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-125A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-125A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-125A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-125A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-125A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-125A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-125A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-125A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-125A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-125A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-125A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 3P
UTS150-H-FTU-150A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-150A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-150A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-150A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-150A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-150A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-150A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-150A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-150A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-150A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-150A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-150A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 3P
UTS150-H-FMU-40A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 2P
UTS150-H-FMU-40A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 3P
UTS150-HT-FMU-40A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 2P
UTS150-HT-FMU-40A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 3P
UTS150-L-FMU-40A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 2P
UTS150-L-FMU-40A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 3P
UTS150-LT-FMU-40A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 2P
UTS150-LT-FMU-40A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 3P
UTS150-N-FMU-40A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 2P
UTS150-N-FMU-40A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 3P
UTS150-NT-FMU-40A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 2P
UTS150-NT-FMU-40A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 3P
UTS150-H-FMU-60A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 2P
UTS150-H-FMU-60A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 3P
UTS150-HT-FMU-60A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 2P
UTS150-HT-FMU-60A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 3P
UTS150-L-FMU-60A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 2P
UTS150-L-FMU-60A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 3P
UTS150-LT-FMU-60A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 2P
UTS150-LT-FMU-60A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 3P
UTS150-N-FMU-60A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 2P
UTS150-N-FMU-60A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 3P
UTS150-NT-FMU-60A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 2P
UTS150-NT-FMU-60A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 3P
UTS150-H-FMU-80A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 2P
UTS150-H-FMU-80A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 3P
UTS150-HT-FMU-80A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 2P
UTS150-HT-FMU-80A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 3P
UTS150-L-FMU-80A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 2P
UTS150-L-FMU-80A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 3P
UTS150-LT-FMU-80A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 2P
UTS150-LT-FMU-80A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 3P
UTS150-N-FMU-80A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 2P
UTS150-N-FMU-80A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 3P
UTS150-NT-FMU-80A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 2P
UTS150-NT-FMU-80A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 3P
UTS150-H-FMU-100A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-H-FMU-100A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-HT-FMU-100A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-HT-FMU-100A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-L-FMU-100A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-L-FMU-100A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-LT-FMU-100A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-LT-FMU-100A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-N-FMU-100A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-N-FMU-100A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-NT-FMU-100A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-NT-FMU-100A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-H-FMU-125A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-H-FMU-125A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-HT-FMU-125A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-HT-FMU-125A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-L-FMU-125A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-L-FMU-125A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-LT-FMU-125A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-LT-FMU-125A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-N-FMU-125A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-N-FMU-125A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-NT-FMU-125A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-NT-FMU-125A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-H-FMU-150A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-H-FMU-150A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-HT-FMU-150A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-HT-FMU-150A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-L-FMU-150A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-L-FMU-150A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-LT-FMU-150A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-LT-FMU-150A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-N-FMU-150A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-N-FMU-150A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-NT-FMU-150A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-NT-FMU-150A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-H-ATU-100A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-H-ATU-100A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-HT-ATU-100A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-HT-ATU-100A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-L-ATU-100A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-L-ATU-100A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-LT-ATU-100A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-LT-ATU-100A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-N-ATU-100A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-N-ATU-100A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-NT-ATU-100A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-NT-ATU-100A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-H-ATU-125A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-H-ATU-125A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-HT-ATU-125A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-HT-ATU-125A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-L-ATU-125A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-L-ATU-125A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-LT-ATU-125A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-LT-ATU-125A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-N-ATU-125A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-N-ATU-125A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-NT-ATU-125A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-NT-ATU-125A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-H-ATU-150A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-H-ATU-150A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-HT-ATU-150A-2P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-HT-ATU-150A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-L-ATU-150A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-L-ATU-150A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-LT-ATU-150A-2P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-LT-ATU-150A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-N-ATU-150A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-N-ATU-150A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-NT-ATU-150A-2P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-NT-ATU-150A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-H-ETS23-60A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 60 A | Setting: Ir 15-60 A | Poles: 3P
UTS150-HT-ETS23-60A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 60 A | Setting: Ir 15-60 A | Poles: 3P
UTS150-L-ETS23-60A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 60 A | Setting: Ir 15-60 A | Poles: 3P
UTS150-LT-ETS23-60A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 60 A | Setting: Ir 15-60 A | Poles: 3P
UTS150-N-ETS23-60A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 60 A | Setting: Ir 15-60 A | Poles: 3P
UTS150-NT-ETS23-60A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 60 A | Setting: Ir 15-60 A | Poles: 3P
UTS150-H-ETS23-100A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 100 A | Setting: Ir 40-100 A | Poles: 3P
UTS150-HT-ETS23-100A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 100 A | Setting: Ir 40-100 A | Poles: 3P
UTS150-L-ETS23-100A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 100 A | Setting: Ir 40-100 A | Poles: 3P
UTS150-LT-ETS23-100A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 100 A | Setting: Ir 40-100 A | Poles: 3P
UTS150-N-ETS23-100A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 100 A | Setting: Ir 40-100 A | Poles: 3P
UTS150-NT-ETS23-100A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 100 A | Setting: Ir 40-100 A | Poles: 3P
UTS150-H-ETS23-150A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 150 A | Setting: Ir 60-150 A | Poles: 3P
UTS150-HT-ETS23-150A-3P-UL Type: HT, 65 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 150 A | Setting: Ir 60-150 A | Poles: 3P
UTS150-L-ETS23-150A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 150 A | Setting: Ir 60-150 A | Poles: 3P
UTS150-LT-ETS23-150A-3P-UL Type: LT, 100 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 150 A | Setting: Ir 60-150 A | Poles: 3P
UTS150-N-ETS23-150A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 150 A | Setting: Ir 60-150 A | Poles: 3P
UTS150-NT-ETS23-150A-3P-UL Type: NT, 35 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 150 A | Setting: Ir 60-150 A | Poles: 3P
UTS150-H-MCS-150A-2P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: MCS molded case switch | Rated current In: 150 A | Setting: Ii fixed 10 x In | Poles: 2P
UTS150-H-MCS-150A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: MCS molded case switch | Rated current In: 150 A | Setting: Ii fixed 10 x In | Poles: 3P
UTS150-L-MCS-150A-2P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: MCS molded case switch | Rated current In: 150 A | Setting: Ii fixed 10 x In | Poles: 2P
UTS150-L-MCS-150A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: MCS molded case switch | Rated current In: 150 A | Setting: Ii fixed 10 x In | Poles: 3P
UTS150-N-MCS-150A-2P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: MCS molded case switch | Rated current In: 150 A | Setting: Ii fixed 10 x In | Poles: 2P
UTS150-N-MCS-150A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: MCS molded case switch | Rated current In: 150 A | Setting: Ii fixed 10 x In | Poles: 3P
UTS150-H-MCP-1.6A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 1.6 A | Setting: Ii 10-20 A | Poles: 3P
UTS150-L-MCP-1.6A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 1.6 A | Setting: Ii 10-20 A | Poles: 3P
UTS150-N-MCP-1.6A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 1.6 A | Setting: Ii 10-20 A | Poles: 3P
UTS150-H-MCP-3.2A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 3.2 A | Setting: Ii 20-40 A | Poles: 3P
UTS150-L-MCP-3.2A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 3.2 A | Setting: Ii 20-40 A | Poles: 3P
UTS150-N-MCP-3.2A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 3.2 A | Setting: Ii 20-40 A | Poles: 3P
UTS150-H-MCP-6.3A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 6.3 A | Setting: Ii 40-80 A | Poles: 3P
UTS150-L-MCP-6.3A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 6.3 A | Setting: Ii 40-80 A | Poles: 3P
UTS150-N-MCP-6.3A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 6.3 A | Setting: Ii 40-80 A | Poles: 3P
UTS150-H-MCP-12A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 12 A | Setting: Ii 70-140 A | Poles: 3P
UTS150-L-MCP-12A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 12 A | Setting: Ii 70-140 A | Poles: 3P
UTS150-N-MCP-12A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 12 A | Setting: Ii 70-140 A | Poles: 3P
UTS150-H-MCP-20A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 20 A | Setting: Ii 120-240 A | Poles: 3P
UTS150-L-MCP-20A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 20 A | Setting: Ii 120-240 A | Poles: 3P
UTS150-N-MCP-20A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 20 A | Setting: Ii 120-240 A | Poles: 3P
UTS150-H-MCP-32A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 32 A | Setting: Ii 190-380 A | Poles: 3P
UTS150-L-MCP-32A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 32 A | Setting: Ii 190-380 A | Poles: 3P
UTS150-N-MCP-32A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 32 A | Setting: Ii 190-380 A | Poles: 3P
UTS150-H-MCP-50A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 50 A | Setting: Ii 300-600 A | Poles: 3P
UTS150-L-MCP-50A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 50 A | Setting: Ii 300-600 A | Poles: 3P
UTS150-N-MCP-50A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 50 A | Setting: Ii 300-600 A | Poles: 3P
UTS150-H-MCP-60A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 60 A | Setting: Ii 400-800 A | Poles: 3P
UTS150-L-MCP-60A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 60 A | Setting: Ii 400-800 A | Poles: 3P
UTS150-N-MCP-60A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 60 A | Setting: Ii 400-800 A | Poles: 3P
UTS150-H-MCP-100A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 100 A | Setting: Ii 600-1200 A | Poles: 3P
UTS150-L-MCP-100A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 100 A | Setting: Ii 600-1200 A | Poles: 3P
UTS150-N-MCP-100A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 100 A | Setting: Ii 600-1200 A | Poles: 3P
UTS150-H-MCP-150A-3P-UL Type: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 150 A | Setting: Ii 900-1800 A | Poles: 3P
UTS150-L-MCP-150A-3P-UL Type: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 150 A | Setting: Ii 900-1800 A | Poles: 3P
UTS150-N-MCP-150A-3P-UL Type: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 150 A | Setting: Ii 900-1800 A | Poles: 3P
Molded Case Circuit BreakersLS Electric
270 product codes available in this family
Sourced direct from KoreaExport-ready supplyCompetitive pricing

Need a different model, or a part not listed here? Send us your parts list →

LS Electric Susol UTS150 UL 489 MCCB (1.6-150 A)

Brand LS Electric·Molded Case Circuit Breakers

Available part numbers (270)

UTS150-H-FTU-40A-2P-UL, UTS150-H-FTU-40A-3P-UL, UTS150-HT-FTU-40A-2P-UL, UTS150-HT-FTU-40A-3P-UL, UTS150-L-FTU-40A-2P-UL, UTS150-L-FTU-40A-3P-UL, UTS150-LT-FTU-40A-2P-UL, UTS150-LT-FTU-40A-3P-UL, UTS150-N-FTU-40A-2P-UL, UTS150-N-FTU-40A-3P-UL + 260 more — see full table ↓

How to order

Send the LS Electric part numbers and quantities through our RFQ form or to info@prosourcemro.com. We confirm price, availability and lead time within 1 business day — no account needed.

RFQ List 0 →
View full details
Product codes & specifications
0 selected
RFQ List (0)
Product codeSpec
UTS150-H-FTU-40A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-40A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-40A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-40A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-40A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-40A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-40A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-40A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-40A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-40A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-40A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-40A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 40 A | Setting: Fixed | Poles: 3P
UTS150-H-FTU-50A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-50A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-50A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-50A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-50A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-50A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-50A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-50A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-50A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-50A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-50A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-50A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 50 A | Setting: Fixed | Poles: 3P
UTS150-H-FTU-60A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-60A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-60A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-60A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-60A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-60A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-60A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-60A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-60A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-60A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-60A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-60A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 60 A | Setting: Fixed | Poles: 3P
UTS150-H-FTU-70A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-70A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-70A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-70A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-70A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-70A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-70A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-70A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-70A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-70A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-70A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-70A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 70 A | Setting: Fixed | Poles: 3P
UTS150-H-FTU-80A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-80A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-80A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-80A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-80A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-80A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-80A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-80A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-80A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-80A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-80A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-80A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 80 A | Setting: Fixed | Poles: 3P
UTS150-H-FTU-90A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-90A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-90A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-90A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-90A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-90A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-90A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-90A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-90A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-90A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-90A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-90A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 90 A | Setting: Fixed | Poles: 3P
UTS150-H-FTU-100A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-100A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-100A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-100A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-100A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-100A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-100A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-100A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-100A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-100A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-100A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-100A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 100 A | Setting: Fixed | Poles: 3P
UTS150-H-FTU-125A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-125A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-125A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-125A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-125A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-125A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-125A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-125A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-125A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-125A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-125A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-125A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 125 A | Setting: Fixed | Poles: 3P
UTS150-H-FTU-150A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 2P
UTS150-H-FTU-150A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 3P
UTS150-HT-FTU-150A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 2P
UTS150-HT-FTU-150A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 3P
UTS150-L-FTU-150A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 2P
UTS150-L-FTU-150A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 3P
UTS150-LT-FTU-150A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 2P
UTS150-LT-FTU-150A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 3P
UTS150-N-FTU-150A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 2P
UTS150-N-FTU-150A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 3P
UTS150-NT-FTU-150A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 2P
UTS150-NT-FTU-150A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FTU (fixed thermal, fixed magnetic) | Rated current In: 150 A | Setting: Fixed | Poles: 3P
UTS150-H-FMU-40A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 2P
UTS150-H-FMU-40A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 3P
UTS150-HT-FMU-40A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 2P
UTS150-HT-FMU-40A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 3P
UTS150-L-FMU-40A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 2P
UTS150-L-FMU-40A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 3P
UTS150-LT-FMU-40A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 2P
UTS150-LT-FMU-40A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 3P
UTS150-N-FMU-40A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 2P
UTS150-N-FMU-40A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 3P
UTS150-NT-FMU-40A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 2P
UTS150-NT-FMU-40A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 40 A | Setting: Ir 32-40 A | Poles: 3P
UTS150-H-FMU-60A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 2P
UTS150-H-FMU-60A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 3P
UTS150-HT-FMU-60A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 2P
UTS150-HT-FMU-60A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 3P
UTS150-L-FMU-60A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 2P
UTS150-L-FMU-60A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 3P
UTS150-LT-FMU-60A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 2P
UTS150-LT-FMU-60A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 3P
UTS150-N-FMU-60A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 2P
UTS150-N-FMU-60A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 3P
UTS150-NT-FMU-60A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 2P
UTS150-NT-FMU-60A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 60 A | Setting: Ir 48-60 A | Poles: 3P
UTS150-H-FMU-80A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 2P
UTS150-H-FMU-80A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 3P
UTS150-HT-FMU-80A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 2P
UTS150-HT-FMU-80A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 3P
UTS150-L-FMU-80A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 2P
UTS150-L-FMU-80A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 3P
UTS150-LT-FMU-80A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 2P
UTS150-LT-FMU-80A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 3P
UTS150-N-FMU-80A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 2P
UTS150-N-FMU-80A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 3P
UTS150-NT-FMU-80A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 2P
UTS150-NT-FMU-80A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 80 A | Setting: Ir 64-80 A | Poles: 3P
UTS150-H-FMU-100A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-H-FMU-100A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-HT-FMU-100A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-HT-FMU-100A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-L-FMU-100A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-L-FMU-100A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-LT-FMU-100A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-LT-FMU-100A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-N-FMU-100A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-N-FMU-100A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-NT-FMU-100A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-NT-FMU-100A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-H-FMU-125A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-H-FMU-125A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-HT-FMU-125A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-HT-FMU-125A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-L-FMU-125A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-L-FMU-125A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-LT-FMU-125A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-LT-FMU-125A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-N-FMU-125A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-N-FMU-125A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-NT-FMU-125A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-NT-FMU-125A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-H-FMU-150A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-H-FMU-150A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-HT-FMU-150A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-HT-FMU-150A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-L-FMU-150A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-L-FMU-150A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-LT-FMU-150A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-LT-FMU-150A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-N-FMU-150A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-N-FMU-150A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-NT-FMU-150A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-NT-FMU-150A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: FMU (adj. thermal, fixed magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-H-ATU-100A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-H-ATU-100A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-HT-ATU-100A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-HT-ATU-100A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-L-ATU-100A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-L-ATU-100A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-LT-ATU-100A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-LT-ATU-100A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-N-ATU-100A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-N-ATU-100A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-NT-ATU-100A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 2P
UTS150-NT-ATU-100A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 100 A | Setting: Ir 80-100 A | Poles: 3P
UTS150-H-ATU-125A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-H-ATU-125A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-HT-ATU-125A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-HT-ATU-125A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-L-ATU-125A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-L-ATU-125A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-LT-ATU-125A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-LT-ATU-125A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-N-ATU-125A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-N-ATU-125A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-NT-ATU-125A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 2P
UTS150-NT-ATU-125A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 125 A | Setting: Ir 100-125 A | Poles: 3P
UTS150-H-ATU-150A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-H-ATU-150A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-HT-ATU-150A-2P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-HT-ATU-150A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-L-ATU-150A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-L-ATU-150A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-LT-ATU-150A-2P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-LT-ATU-150A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-N-ATU-150A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-N-ATU-150A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-NT-ATU-150A-2P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 2P
UTS150-NT-ATU-150A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: ATU (adj. thermal, adj. magnetic) | Rated current In: 150 A | Setting: Ir 120-150 A | Poles: 3P
UTS150-H-ETS23-60A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 60 A | Setting: Ir 15-60 A | Poles: 3P
UTS150-HT-ETS23-60A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 60 A | Setting: Ir 15-60 A | Poles: 3P
UTS150-L-ETS23-60A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 60 A | Setting: Ir 15-60 A | Poles: 3P
UTS150-LT-ETS23-60A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 60 A | Setting: Ir 15-60 A | Poles: 3P
UTS150-N-ETS23-60A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 60 A | Setting: Ir 15-60 A | Poles: 3P
UTS150-NT-ETS23-60A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 60 A | Setting: Ir 15-60 A | Poles: 3P
UTS150-H-ETS23-100A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 100 A | Setting: Ir 40-100 A | Poles: 3P
UTS150-HT-ETS23-100A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 100 A | Setting: Ir 40-100 A | Poles: 3P
UTS150-L-ETS23-100A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 100 A | Setting: Ir 40-100 A | Poles: 3P
UTS150-LT-ETS23-100A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 100 A | Setting: Ir 40-100 A | Poles: 3P
UTS150-N-ETS23-100A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 100 A | Setting: Ir 40-100 A | Poles: 3P
UTS150-NT-ETS23-100A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 100 A | Setting: Ir 40-100 A | Poles: 3P
UTS150-H-ETS23-150A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 150 A | Setting: Ir 60-150 A | Poles: 3P
UTS150-HT-ETS23-150A-3P-ULType: HT, 65 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 150 A | Setting: Ir 60-150 A | Poles: 3P
UTS150-L-ETS23-150A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 150 A | Setting: Ir 60-150 A | Poles: 3P
UTS150-LT-ETS23-150A-3P-ULType: LT, 100 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 150 A | Setting: Ir 60-150 A | Poles: 3P
UTS150-N-ETS23-150A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 150 A | Setting: Ir 60-150 A | Poles: 3P
UTS150-NT-ETS23-150A-3P-ULType: NT, 35 kA at 480 V, 100% rated | Trip unit: ETS23 electronic (LI/LSI/LIG) | Rated current In: 150 A | Setting: Ir 60-150 A | Poles: 3P
UTS150-H-MCS-150A-2P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: MCS molded case switch | Rated current In: 150 A | Setting: Ii fixed 10 x In | Poles: 2P
UTS150-H-MCS-150A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: MCS molded case switch | Rated current In: 150 A | Setting: Ii fixed 10 x In | Poles: 3P
UTS150-L-MCS-150A-2P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: MCS molded case switch | Rated current In: 150 A | Setting: Ii fixed 10 x In | Poles: 2P
UTS150-L-MCS-150A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: MCS molded case switch | Rated current In: 150 A | Setting: Ii fixed 10 x In | Poles: 3P
UTS150-N-MCS-150A-2P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: MCS molded case switch | Rated current In: 150 A | Setting: Ii fixed 10 x In | Poles: 2P
UTS150-N-MCS-150A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: MCS molded case switch | Rated current In: 150 A | Setting: Ii fixed 10 x In | Poles: 3P
UTS150-H-MCP-1.6A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 1.6 A | Setting: Ii 10-20 A | Poles: 3P
UTS150-L-MCP-1.6A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 1.6 A | Setting: Ii 10-20 A | Poles: 3P
UTS150-N-MCP-1.6A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 1.6 A | Setting: Ii 10-20 A | Poles: 3P
UTS150-H-MCP-3.2A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 3.2 A | Setting: Ii 20-40 A | Poles: 3P
UTS150-L-MCP-3.2A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 3.2 A | Setting: Ii 20-40 A | Poles: 3P
UTS150-N-MCP-3.2A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 3.2 A | Setting: Ii 20-40 A | Poles: 3P
UTS150-H-MCP-6.3A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 6.3 A | Setting: Ii 40-80 A | Poles: 3P
UTS150-L-MCP-6.3A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 6.3 A | Setting: Ii 40-80 A | Poles: 3P
UTS150-N-MCP-6.3A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 6.3 A | Setting: Ii 40-80 A | Poles: 3P
UTS150-H-MCP-12A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 12 A | Setting: Ii 70-140 A | Poles: 3P
UTS150-L-MCP-12A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 12 A | Setting: Ii 70-140 A | Poles: 3P
UTS150-N-MCP-12A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 12 A | Setting: Ii 70-140 A | Poles: 3P
UTS150-H-MCP-20A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 20 A | Setting: Ii 120-240 A | Poles: 3P
UTS150-L-MCP-20A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 20 A | Setting: Ii 120-240 A | Poles: 3P
UTS150-N-MCP-20A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 20 A | Setting: Ii 120-240 A | Poles: 3P
UTS150-H-MCP-32A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 32 A | Setting: Ii 190-380 A | Poles: 3P
UTS150-L-MCP-32A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 32 A | Setting: Ii 190-380 A | Poles: 3P
UTS150-N-MCP-32A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 32 A | Setting: Ii 190-380 A | Poles: 3P
UTS150-H-MCP-50A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 50 A | Setting: Ii 300-600 A | Poles: 3P
UTS150-L-MCP-50A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 50 A | Setting: Ii 300-600 A | Poles: 3P
UTS150-N-MCP-50A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 50 A | Setting: Ii 300-600 A | Poles: 3P
UTS150-H-MCP-60A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 60 A | Setting: Ii 400-800 A | Poles: 3P
UTS150-L-MCP-60A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 60 A | Setting: Ii 400-800 A | Poles: 3P
UTS150-N-MCP-60A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 60 A | Setting: Ii 400-800 A | Poles: 3P
UTS150-H-MCP-100A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 100 A | Setting: Ii 600-1200 A | Poles: 3P
UTS150-L-MCP-100A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 100 A | Setting: Ii 600-1200 A | Poles: 3P
UTS150-N-MCP-100A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 100 A | Setting: Ii 600-1200 A | Poles: 3P
UTS150-H-MCP-150A-3P-ULType: H, 65 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 150 A | Setting: Ii 900-1800 A | Poles: 3P
UTS150-L-MCP-150A-3P-ULType: L, 100 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 150 A | Setting: Ii 900-1800 A | Poles: 3P
UTS150-N-MCP-150A-3P-ULType: N, 35 kA at 480 V, 80% rated | Trip unit: MCP motor circuit protector | Rated current In: 150 A | Setting: Ii 900-1800 A | Poles: 3P

Need a different model, or a part not listed here? Send us your parts list →