When the tertiary voltage of the grounding potential transformer rises over a given value, the main contact closes after a time delay to trip a circuit breaker; suitable for ground fault detection on distribution lines.

Key features

  • Ground fault detection via GPT tertiary voltage
  • ICS coil options: DC current 0.2/2.0 A, 0.5/2.0 A, 1.0 A; DC voltage 24/110/125 V; AC current 0.5/1.0/2.0 A; AC voltage 110/220 V

Specifications

Frequency 60 Hz (standard), 50 Hz (option)
Case Color Munsell N1.5
GVG-C9 Rating: 190 V | Taps: 35, 40, 45, 50, 55, 60, 65 V | ICS Unit: DC 1.0 A | Case: Non-drawout | Weight: approx. 3 kg
GVG-C1 Rating: 110 V | Taps: 20, 25, 30, 35, 40 V | ICS Unit: DC 1.0 A | Case: Non-drawout | Weight: approx. 3 kg
GVG-CD9 Rating: 190 V | Taps: 35, 40, 45, 50, 55, 60, 65 V | ICS Unit: DC 0.5/2.0 A | Case: Drawout | Weight: approx. 4 kg
GVG-CD1 Rating: 110 V | Taps: 20, 25, 30, 35, 40 V | ICS Unit: DC 0.5/2.0 A | Case: Drawout | Weight: approx. 4 kg
Induction Protective RelaysKyongbo Electric
4 product codes available in this family
Sourced direct from KoreaExport-ready supplyCompetitive pricing

Need a different model, or a part not listed here? Send us your parts list →

Kyongbo Electric Induction Over Voltage Ground Relay GVG-C (Normally Open Contact)

Brand Kyongbo Electric·Induction Protective Relays

Available part numbers (4)

GVG-C9, GVG-C1, GVG-CD9, GVG-CD1

How to order

Send the Kyongbo Electric part numbers and quantities through our RFQ form or to info@prosourcemro.com. We confirm price, availability and lead time within 1 business day — no account needed.

RFQ List 0 →
View full details
Product codes & specifications
0 selected
RFQ List (0)
Product codeSpec
GVG-C9Rating: 190 V | Taps: 35, 40, 45, 50, 55, 60, 65 V | ICS Unit: DC 1.0 A | Case: Non-drawout | Weight: approx. 3 kg
GVG-C1Rating: 110 V | Taps: 20, 25, 30, 35, 40 V | ICS Unit: DC 1.0 A | Case: Non-drawout | Weight: approx. 3 kg
GVG-CD9Rating: 190 V | Taps: 35, 40, 45, 50, 55, 60, 65 V | ICS Unit: DC 0.5/2.0 A | Case: Drawout | Weight: approx. 4 kg
GVG-CD1Rating: 110 V | Taps: 20, 25, 30, 35, 40 V | ICS Unit: DC 0.5/2.0 A | Case: Drawout | Weight: approx. 4 kg